nightclubs – FIRE, EVACUATION AND CROWD SAFETY BLOG http://fseg.gre.ac.uk/blog Fri, 23 May 2014 10:11:29 +0000 en-US hourly 1 https://wordpress.org/?v=4.8.2 Yet another Nightclub Tragedy — Grief tainted with Anger http://fseg.gre.ac.uk/blog/?p=294 http://fseg.gre.ac.uk/blog/?p=294#comments Tue, 29 Jan 2013 14:50:53 +0000 http://fseg.gre.ac.uk/blog/?p=294 Continue reading ]]> The death toll in the Kiss Nightclub fire has risen to 231.  It is heart breaking to see so many young faces with promising lives ahead of them snuffed out in seconds.  The names of the victims are listed on a Brazilian newspaper website along with their photos:

http://g1.globo.com/rs/rio-grande-do-sul/noticia/2013/01/conheca-vitimas-do-incendio-em-casa-noturna-em-santa-maria-rs.html

It is even more heartbreaking to learn that this tragic loss of life may have been needless and preventable.  As more details of this tragedy begin to emerge, heartbreak turns to anger.  While the details are still not known for certain, the more that comes out in the media the more this carnage appears to have been a preventable tragedy and a failure of regulation, enforcement and management.

What do we know from the reports in the media:

1) From CNN we are told that the club’s license had expired in August 2012 and had not been renewed.  We are also told that the owners had said that the club was properly permitted and had been inspected by the fire marshal.

http://edition.cnn.com/2013/01/28/world/americas/brazil-nightclub-fire-main/index.html

According to reports on CNN, a state fire official suggested that the maximum capacity of the club was 1000 people.

http://edition.cnn.com/2013/01/28/world/americas/brazil-nightclub-fire/index.html

This suggests that at least up to August 2012 the club had been considered appropriate and compliant with the local codes.

2) It has been reported in most media accounts that the club had only one exit.  In some media accounts the word emergency exit has been used, which suggests that there may be at least two exits, while in other accounts it has been categorically stated that the club had just one exit.

http://www.guardian.co.uk/world/2013/jan/28/brazil-nightclub-fire-police-question

A schematic of the club on a Brazilian web site shows only a single exit (also see below).

http://g1.globo.com/rs/rio-grande-do-sul/tragedia-incendio-boate-santa-maria-entenda/platb

3) Most recent reports suggest that fire and rescue officials estimate that there were 1500 people in the club at the time of the incident.

http://g1.globo.com/rs/rio-grande-do-sul/tragedia-incendio-boate-santa-maria-entenda/platb

4) While it is still not confirmed, it now appears likely that the band did make use of pyrotechnics during their show, and this was a well known feature of the band.  Reports have even suggested that they made use of three flares.

http://www.guardian.co.uk/world/2013/jan/28/brazil-nightclub-fire-police-question

http://www.bbc.co.uk/news/business-21196209

http://www.nytimes.com/2013/01/29/world/americas/brazil-fire-nightclub.html?_r=0

It is not clear what is meant by a flare, but it is likely to be more than a sparkler!

5) All accounts so far suggest that the fire started in foam sound proofing and spread rapidly.

http://edition.cnn.com/2013/01/28/world/americas/brazil-nightclub-fire/index.html

However, the fire cause is not known at this stage.  It may, as media accounts suggest, have been caused by the pyrotechnics, or it may have been caused by an electrical fault.  We simply do not know at this stage.

6) The exit route was dark.

http://edition.cnn.com/2013/01/28/world/americas/brazil-nightclub-fire/index.html

7) In none of the accounts that I have read is mention of a fire alarm sounding.

8) At first security guards thought that there was a fight or that people were trying to leave without paying so they initially blocked the exit.

http://edition.cnn.com/2013/01/28/world/americas/brazil-nightclub-fire/index.html

9) Reports have highlighted that many bodies were found in the toilets.

10) Reports have suggested that at least one fire extinguisher failed to operate.

http://news.sky.com/story/1043674/brazil-nightclub-fire-security-blocked-exit

Taking these points one can begin to ask some questions concerning the Brazilian fire safety regulations, the enforcement of those regulations and the quality of the management at the club.

REGULATIONS and ENFORCEMENT:

a) How could Brazilian building regulations (or the local code) permit a place of public assembly, with a reported capacity of 1000 people, to have only a single exit?  Even though the license had expired and was under review, the club was considered compliant up to when the license expired in August 2012, so the exit capacity was deemed to be acceptable. Furthermore, what total exit width is required by regulation?   With a capacity of 1000 people I would have expected at least three exits with a total exit width of at least 6m.

b) It appears that no fire alarm sounded.  Was this because the alarm failed or did the club not have an alarm?  If the club did not have an alarm, how could the building regulations possibly permit this?  Had an alarm sounded, perhaps the security guards would not have initially prevented people from escaping, possibly reducing the death toll.  If the club had an alarm was it operational prior to the fire?  If not, could this have been overlooked during a fire inspection?

c) It is reported that the exit route was dark.  Was there no emergency lighting in the club or did it fail?  If there was no emergency lighting how could this be permitted by the regulations?  Had emergency lighting been available, perhaps people would not have tripped in the exit path and perhaps people would not have mistaken the toilets for an exit route. If the club had emergency lighting was it operational prior to the fire?  If not, could this have been overlooked during a fire inspection?

Schematic of the Kiss Nightclub

d) What does the Brazilian code require in terms of emergency exit signage?  Is this required?  Had it been in place, perhaps so many people would not have mistaken the toilets as a means of escape. If emergency exit signage was required by law and it was in place, was it operational prior to the fire?  If not, could this have been overlooked during a fire inspection?

e) The fire appears to have started in the sound proofing foam that lined the ceiling and spread rapidly producing large amounts of toxic fumes.  What type of foam was this?  Was it protected in some way e.g. coated or covered with a fire resistive material?  What do the Brazilian fire regulations say about the type of foams that can be used in places of assembly?  If the use of foam is permitted, was the foam in place compliant with standards prior to the fire?  If not, could this have been overlooked during a fire inspection?

f) What do Brazilian regulations say about the use of indoor pyrotechnics?  If like most countries they permit the use of such devices, what provisions are made to limit their use and ensure that they are used in a responsible manner?   Concerning the use of flares, surely this cannot be permitted?

g) Is it required by Brazilian fire regulations to regularly inspect mandatory fire fighting equipment? If so, what is the frequency?  If regulations stipulate they are to be inspected, were the fire extinguishers in the club inspected prior to the fire?

MANAGEMENT:

a) It is reported that the maximum occupancy for the club was 1000, yet fire authorities suggest that there could have been as many 1500 people in the club.  What means did management have to ensure that the number of people in the club did not exceed their license limit?

b) If the use of pyrotechnics are permitted under Brazilian code, what measures did the management have in place to ensure their safe use?

c) It is reported that fire extinguishers failed to operate.  Did the club management have the fire extinguishers serviced on a regular basis?

d) What training did the club staff have in terms of fire fighting and crowd management?

These are just some of the questions that need to be answered if the root causes of this tragedy are to be addressed.  It is possible that this tragedy was no accident i.e. an unforeseeable event, but the result of a predictable and preventable failing of Regulation, Enforcement and Management.  If so, then immediate measures must be taken to correct the failings in order to ensure a safer Brazil – let this be the legacy of the Kiss Nightclub victims.

Finally, this tragedy provides a couple of hard learnt lessons for the rest of the world:

1) Stop the use of pyrotechnics indoors, they are just too dangerous.

2) Inspection and enforcement must be taken as seriously as legislation.

]]>
http://fseg.gre.ac.uk/blog/?feed=rss2&p=294 2
Yet another Tragic Nightclub Fire! http://fseg.gre.ac.uk/blog/?p=283 http://fseg.gre.ac.uk/blog/?p=283#comments Sun, 27 Jan 2013 11:51:32 +0000 http://fseg.gre.ac.uk/blog/?p=283 Continue reading ]]> Today we hear the news of a tragic nightclub fire in Brazil which has claimed the lives of at least 180 young people, with at least 200 more injured.  The fire is reported to have occurred in the early hours of the morning of the 27 January in the Kiss Nightclub in Santa Maria,Rio Grande do Sul in southern Brazil.  According to unconfirmed reports in The Independent newspaper, the fire allegedly started when a band member started a fireworks display on stage which set alight sound proofing.  While the nature of the sound proofing has not yet been confirmed, it was probably (untreated) Polyurethane (PU) foam, which is cheap to obtain and easy to put up.  If correct, this will be frighteningly similar to the Station Nightclub fire in Rhode Island USA of February 2003 which claimed the lives of 100 people and injured over 200 others.

In the Rhode Island case, fire works started by the band set alight PU foam which was used as sound proofing cladding on the walls.  The PU rapidly burnt producing thick choking smoke, laden with deadly Carbon Monoxide gas and Hydrogen Cyanide gas.  People were rapidly overcome by the toxic gases and the rapid resulting flashover.  Coupled fire and evacuation computer simulations of the Rhode Island nightclub fire produced by FSEG suggest that after approximately 100 seconds from ignition, around 100 people would be dead due to the inhalation of toxic fire gases and the effects of flashover.  In the Rhode Island case, while the club was full, it was within legal limits and the nightclub had four exits (including the main exit), but the majority of the patrons tried to use the main entrance, the exit that they used to come into the club.

Media accounts are suggesting that between 300 and 2000 people were in the Kiss Nightclub at the time of the fire.  It is also not clear how many exits the nightclub had, media reports suggest that the nightclub had only one emergency exit and that fire fighters had to make a hole in the wall to assist people to escape.  As the Rhode Island Nightclub fire demonstrated, fires in such environments, fuelled by PU foam will spread extremely rapidly producing large amounts of highly toxic gases, providing people in the crowed venue little time to get out.

If the reports in the media are correct, then it is surprising that only 180 people have lost their lives.  I would not be surprised if the death toll rises, especially if the occupancy is more than 300.  Large crowds, within a confined space, whose walls are clad with combustible PU foam, with limited means of egress, probably in the dark, a number of who are probably intoxicated and then allowing the use of pyrotechnics is a recipe for disaster.   Indeed, building regulations and planning permission should not permit such death traps to exist in the first place and enforcement authorities should ensure that they do not occur.

Once the blame game starts, I hope that the bereaved families do not simply point their finger at the nightclub owner but look beyond this, to their local government authorities that have responsibility for planning permission and building control and to enforcement authorities that have responsibility for inspecting premises.  It is too easy to simply blame the owner.  More importantly, to do so will simply allow this type of tragedy to happen again and again.

Furthermore, while this type of disaster can happen anywhere in the world, and it has — USA, Russia, China and Argentina to name just four recent disasters – it is to be hoped that a country with the responsibility of hosting the next Football World Cup and the Olympics, will ensure that their building regulations and the enforcement of those regulations are fit for purpose.   Not simply for the new build stadia, but for all the existing hotels, transportation hubs and entertainment venues that will be enjoyed by millions of tourists from around the world.

Finally, I wonder how long it is going to take before the media, and local government officials begin to attribute “panic” as a contributory factor in this tragedy, conveniently diverting attention from other potential systemic failures.

BACKGROUND INFORMATION: 

Rhode Island Fire Simulation: https://www.youtube.com/watch?v=o197yeup1BQ&list=PLC82636C7790DE890&index=1

Rhode Island Coupled Fire and Evacuation simulation:

https://www.youtube.com/watch?v=gmPOIriMiyU&list=PL482FD999D5793B82&index=1

Paper describing simulations: http://fseg.gre.ac.uk/fire/pub.asp

Paper 223. “Coupled Fire/Evacuation Analysis of the Station Nightclub Fire”. Galea E.R., Wang, Z., Veeraswamy, A., Jia, F.,Lawrence, P., and Ewer, J. Proceedings of 9th IAFSS SymposiumKarlsruhe,Germany, 2008, ISNN 1817-4299, pp 465-476. DOI:10.3801/IAFSS.FSS.9-465

LINKS TO NEWS ABOUT THIS INCIDENT:

SKY NEWS: Brazil Nightclub Fire Tragedy: 180 Killed.

http://news.sky.com/story/1043501/brazil-nightclub-fire-tragedy-180-killed

The Independent: ‘At least 180 killed’ inBrazilnightclub fire after pyrotechnics set sound-proofing alight

http://www.independent.co.uk/news/world/americas/at-least-180-killed-in-brazil-nightclub-fire-after-pyrotechnics-set-soundproofing-alight-8468600.html

 

]]>
http://fseg.gre.ac.uk/blog/?feed=rss2&p=283 6